Three-phase: CIMR-LC4A_ | 0009 | 0015 | 0018 | 0024 | 0031 | 0039 | 0045 | 0060 | 0075 | 0091 | 0112 | |
Motor kW | For HD setting | 4.0 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 |
Output characteristics | Inverter capacity kVA | 7 | 11.3 | 13.7 | 18.3 | 24 | 30 | 34 | 48 | 57 | 69 | 85 |
Rated output current (A) | 9.2 | 14.8 | 18 | 24 | 31 | 39 | 45 | 60 | 75 | 91 | 112 | |
Max. output voltage | 380..480V (proportional to input voltage) | |||||||||||
Max. output frequency | 120 Hz | |||||||||||
Power supply | Rated input voltage and frequency | 3-phase 380..480 VAC, 50/60 Hz | ||||||||||
Allowable voltage fluctuation | -15%..+10% | |||||||||||
Allowable frequency fluctuation | 5% | |||||||||||
Input Current (A) | 10.4 | 15 | 20 | 29 | 39 | 44 | 49 | 58 | 71 | 86 | 105 |