      Wire Size Rangę (<) Torqu-
  Nnme Description Maximum Minimum M,iximum Recommended
1 Aralog 1/0 Aratog 10 Signals 2.5 mmz (14 AWG) 0.5 mm* (22 AWG) 0.2 N-m 1.8 IbHn. 0.2 N«m 18lt*in
2 Digital Irpuls Digital Input Signals 2.5 mm* (14 AWG) 0.5 mm* (22 WG) 0.2 N-m 1.8lb.-in. 0.2 N«m 1.81 Mn
3 Digital Ouiputs Digilal Oul Relays 2.5 mm* (14 AWG) 0.5 mm* (22 AWG) 0.5 N-m 4.5lb.-in. 0.5 Nnti 4.S It-in

 

No. Signal   Description
1 Analog In 1 (-) 0)   Isolated (9, bipolar, ditferential, 9 bit & sign, 88k ohm input impedance. A jumper fpage 28) selects: 0-10V. ±10V, 4-20mA. Default: 0-10V (Ri =200k), 4-20mA (Ri=100 ohm).
2 Analog In 1 (+) W
3 Analog In 2 (-) (U
4 Analog In 2 (+) (D
5 -10VPotReference - 2k ohm minimum, 10 mA maximum load, 1% accuracy.
6 Pot Common (GND)   For (+) and (-) 10V pot references.
7 +10V Pot Reference - 2kohm minimum, 10mA maximumload, 1%aocuracy.
8 Analog Out 1 (+) (4) Bipolar (current out is not bipolar), 9 bit & sign, 2kohm minimum load. A jumper (seepage_22) selects: 0-10V, ±10V, 4-20mA.
9 Analog Out Common
10 Analog Out 2 (+)
11 Digital In 1 Stop - CF 115V AC. 50/60 Hz - Opto isolated Low State: lessthan 30V AC High State: greaterthan 40V AC 24V DC - Opto isolated (250V) Low State: lessthan 5V DC High State: greater than 20V DC 11.2 mA DC Enable: Digital Input 6 is jumper selectable for HW Enable. On-Time: < 16.7ms, Off-Time < 1 ms
12 Digital In 2 Start
13 Digital In 3 Auto/Man
14 Digital In 4 Speed Sel 1
15 Digital In 5 Speed Sel 2
16 Digital In 6/Hardware Enable, seepg. 22 Speed Sel 3
17 18 Digital In Common   Allows source orsink operation. Terminals 17/18 & 19 can also be used to provide backup power to DPI and control devices.
19 +24VDC(2) - Drive supplied logie input power.
20 24V Common (2) - Common for internal power supply.
21 Digital Out 1 - N.C. P) Fault Max. Resistive Load: 240V AC/30V DC -1200VA, 150W Max. Current: 5A, Min. Load: 10mA
22 Digital Out 1 Common  
23 Digital Out 1 - N.O.0) NOTFault
24 Digital Out 2-N.C. P) NOT Run Max. Inductwe Load: 240V AC/30V DC - 840VA, 105W Max. Current: 3.5A. Min. Load: 10mA
25 Digital Out 2/3 Com.  
26 Digital Out3-N.0.0) Run


WebSystem  tel. 048 383.01.44   | wortal-> www.falowniki.pl | forum-> www.falowniki.info | porównaj-> www.falowniki.com.pl

Warto zobaczyć

Giełda falowników

Falownik Lenze 9300 Vector 110kW

Falownik Lenze 9300 Vector 110kW EVF9335-EVV030

Więcej…

Softstart eTran 7,5kW SET200-7.5

Softstart eTran 7,5kW SET200-7.5

Więcej…

Softstart eTran 11kW SET500-11

Softstart eTran 11kW SET500-11 

Więcej…

Siemens Simovert 45kVA 6SE-1245-2AA00

Siemens Simovert 45kVA 6SE-1245-2AA00

Więcej…

Siemens Simovert 22kVA 6SE-1222-2AA02

Siemens Simovert 22kVA 6SE-1222-2AA02

Więcej…

Siemens Simovert 22kVA 6SE-1222-2AA03

Siemens Simovert 22kVA 6SE-1222-2AA03

Więcej…
dobór falowniki Wortal napędów energoelektronicznych www.falowniki.pi . Napędy energoelektroniczne do regulacji prędkości obrotowej silników elektrycznych.

Copyright © 2010 www.falowniki.pl